Calculating Power Triangle and Power Factor

In AC circuits, the relationship between different types of power (real and reactive and apparent) can be depicted by a right triangle known as the power triangle.

Power Triangles in AC Circuits with Impedance

Our previous lesson covered real and reactive power in AC circuits containing resistance and either capacitance or inductance (or both).

To calculate and draw a power triangle for the total power consumed, we need to know the phase difference between the voltage and current waveforms.

Sine Waves and In-Phase Power:

In AC circuits, voltage and current are sine waves, meaning their strength constantly changes over time.

We know, power equals voltage times current (P = VI).

Maximum power occurs when the voltage and current peaks and zero points perfectly align in time. This alignment is called “in phase.”

Impedance and Phase Shift:

Three main components in an AC circuit impact the voltage, current relationship and their phase difference: resistors, capacitors, and inductors.

These component determine the circuit’s total impedance (Z) which is similar to resistance in DC circuits but measured in ohms. However, in AC circuits, impedance is the ratio of voltage and current phasors created by a circuit element.

Phasors and Impedance Triangles:

Phasors are lines, representing voltage or current amplitude by their length and phase difference with other phasors by their angle relative to them. AC circuits combine resistance and reactance to create a total impedance (Z) that limits current flow.

Importantly, unlike DC circuits, impedance is not a simple sum of resistance and reactance because pure resistance and pure reactance cause a 90° phase shift.

However we can leverage this 90° phase shift, to create a right angled triangle called an impedance triangle.

Impedance acts as the hypotenuse of this triangle, calculated using the Pythagorean theorem. This geometric relationship between resistance and reactance, and impedance is visually represented by the impedance triangle as indicated below:

Impedance Triangle and Power Triangle Relationship

Remember that impedance (Z) is the combined effect of resistance (R) and reactance (X), acting like a vector sum.

It has both a magnitude (absolute value) and a phase angle (Φ) reflecting the phase difference between resistance and reactance.

This triangle’s shape changes based on variations in reactance (X) with frequency, while resistance (R) stays constant.

We can further analyze this concept by transforming the impedance triangle into a power triangle, representing the three key power elements in AC circuits.

Ohms Law defines power (P) in DC circuits as current squared (I²) multiplied by resistance (R).

Applying this logic, we can multiply each side of the impedance triangle by I² to get the corresponding sides of the power triangle:

Understanding Real Power in AC Circuits

Real Power (P): The Workhorse

Real power (P) which is also called true or active power, is the workhorse of an electrical circuit. Measured in watts (W), it represents the power dissipated by the resistive elements.

Unlike reactive power, real power gets used to perform actual work in the circuit, such as heating elements, powering motors, or generating light.

Calculating Real Power in AC and DC Circuits

The good news is that, calculating real power in AC circuits is similar to DC circuits. They both use the formula P = I² * R, where:

Since resistors don’t cause any phase shift between voltage and current waveforms, all the real power gets delivered directly to the resistance and converted into usable forms like heat, light, or mechanical work. This is why, real power is also considered the circuit’s average power.

Impact of Phase Angle (Φ): When Things Get Interesting

However unlike resistors, other components like capacitors and inductors introduce a phase shift (Φ) between voltage and current. This additional factor affects how real power is calculated in AC circuits.

Finding Real Power with Phase Angle

To account for the phase shift, the real power formula gets extended to:

P = I² * R = Vrms * Irms * cos(Φ) (W)

Here:

Focusing on Resistive Circuits: Zero Phase Shift

However it’s important to remember that in a purely resistive circuit (with no capacitors or inductors), the phase difference between voltage and current is zero (Φ = 0°).

Therefore the cosine term (cos(Φ)) in the extended formula becomes 1, and the real power calculation simplifies back to P = I² * R, just like in DC circuits.

Real Power: The Workhorse of the Circuit

Understanding Reactive Power in AC Circuits

Reactive power (Q) also known as wattless power, plays a crucial role in AC circuits. It doesnt contribute to actual work performed in the circuit (like powering a light bulb) but it significantly impacts the phase shift between voltage and current waveforms.

Origins of Reactive Power: Inductors and Capacitors

Reactive power is linked to the reactance caused by inductors and capacitors. Reactance opposes the flow of current in a way that real power (P) doesnt. Unlike DC circuits, AC circuits have reactive power due to these reactive components.

The Push and Pull of Reactive Power

The Takeaway: No Real Work Done

Importantly, both capacitors and inductors, constantly exchange power with the source, meaning they neither truly consume nor generate power in the traditional sense. As a result no real work is done using reactive power (Q).

Calculating Reactive Power

Similar to real power we can calculate reactive power using the formula:

Q = I² * X = Vrms * Irms * sin(Φ) (volt-amperes reactive, VAr)

Here:

Reactive Power and the 90° Phase Shift

In a circuit, containing only a pure reactance (inductor or capacitor), the voltage and current waveforms experience a 90° phase difference.

Because of this.. multiplying the voltage (V) and current (I) by sin(Φ) results in a vertical component.

This is because, the sine function reaches its maximum value (1) at 90° which aligns with the 90° phase shift between voltage and current.

Consequently the resulting value represents the reactive power (Q) in the circuit, as shown in the below formula:

Understanding Apparent Power

We’ve already seen that real power (P) gets used by resistors, while reactive power (Q) interacts with capacitors and inductors. This interaction creates a phase difference between voltage and current waveforms, due to the interplay of these resistive and reactive components.

Complex Power and the Power Triangle

Theres a mathematical relationship between real power (P) and reactive power (Q) called complex power. However the total power delivered to an AC circuit isn’t simply the sum of real and reactive power, instead, it’s the vector sum of these two, represented in volt-amperes (VA) and visualized using the power triangle.

Apparent Power: The “Seeming” Total

The product of the root mean square (rms) voltage (V) applied to the circuit and the rms current (I) flowing through it gives us the “volt-ampere product” (VA) denoted by S. The magnitude of S is commonly known as; apparent power. This apparent power might seem like the total power consumed by the circuit, but it’s a bit misleading.

Why?… Because, apparent power (S) includes both the real power (P) that actually does work (represented by the in-phase component), and the reactive power (Q) which doesn’t directly contribute to work (represented by the out-of-phase component).

The Power Triangle

Identically, to the impedance triangle, the power triangle visually depicts the three key power components in an AC circuit:

This right-angled triangle showcases the relationship between these three power elements providing a graphical understanding of power flow in AC circuits.

Power Triangle Breakdown

The diagram showcases a power triangle which is a valuable tool, for understanding the relationship between different types of power in an AC circuit.

Phase Angle (Φ): This angle indicates, the phase difference between voltage and current waveforms. A larger phase angle signifies a greater presence of reactive power.

Relationship between Power Triangle Sides and Phase Angle:

Understanding Power Factor

Power factor (p.f.) denoted by cos(Φ), is a critical parameter in AC circuits. It reflects how efficiently the circuit utilizes the delivered power.

Calculating Power Factor

Power factor is a dimensionless quantity, calculated as the ratio of real power (P) consumed by the circuit (in watts) to the apparent power (S) delivered by the source (in volt-amperes). This can be expressed as a decimal value (e.g., 0.95) or a percentage (e.g., 95%).

Power Factor and Phase Angle

Power factor is directly linked to the phase angle (Φ) between the voltage (V) and current (I) waveforms in the circuit. Here V and I represent the root mean square (rms) values of voltage and current. Interestingly… the order in which we calculate the phase difference (current with respect to voltage or vice versa) doesnt matter.

The Power Factor Formula

The mathematical relationship between power factor and the phase angle is represented by the formula:

Previously we had discussed that in a purely resistive circuit (containing only resistors), the voltage and current waveforms are perfectly aligned (in-phase) with a zero-degree phase difference (Φ = 0°).

This alignment results in all the delivered power being “real” power (P) used for work. Consequently the apparent power (S) and real power (P) become equal, leading to a power factor (p.f.) of:

In this ideal situation the watts consumed (real power) match the volt-amperes consumed (apparent power), resulting in a unity power factor (1.0 or 100%).

This signifies maximum efficiency, because all delivered power gets used for work.

On the other hand we also saw that in a purely reactive circuit (containing only capacitors or inductors), the voltage and current waveforms are completely out-of-phase, expereincing a 90° phase difference (Φ = 90°).

With this significant phase shift, the power factor becomes:

Here even-though there’s voltage and current flow, the real power consumed (P) is zero because the reactive power (Q) cancels it out. This highlights the inefficiency of purely reactive circuits.

Optimizing Power Factor

Reducing the reactive power component (VAr) in the power triangle has a direct effect on the phase angle (θ). Lowering the reactive power component shrinks the angle (θ) causing the power factor to get closer to unity (1).

Since, a high power factor indicates efficient use of delivered current, it’s desirable in most practical AC circuits.

Power Factor Formula

The relationship between real power (P), apparent power (S), and power factor (p.f.) can be expressed through the formula:

In AC circuits, the phase difference between voltage (V) and current (I) waveforms impacts the power factor (p.f.). Heres how:

Solving a Power Triangle Problem

We have a coil with the following properties:

This coil is connected to an AC power supply with the following specifications:

We’ re interested in solving four parts related to this AC circuit:

(a) Impedance (Z): Calculate the total impedance of the coil which considers both its resistance and inductive reactance.

(b) Current (I): Determine the current flowing through the coil, based on the voltage and impedance.

(c) Power Factor (pf): Find the power factor… a parameter indicating how efficiently the circuit utilizes the supplied power.

(d) Apparent Power (S): Calculate the apparent power which represents the total volt-amperes delivered by the source.

Additionally we want to visualize the relationship between these power components, by drawing the resulting power triangle. This triangle helps us, to understand the inter-play between real power (performing work), reactive power (stored/returned by reactive components), and apparent power.

Now, let us find how much current the coil consumes:

Next, we calculate the power factor and the phase angle Φ:

Next, we will calculate how much Apparent power (S) was consumed by the coil:

Now, let’s draw the power triangle for the coil, as shown below:

As the power triangle relationships of this simple example demonstrates, at a power factor of 0.46 or 46%, the coil requires 156.2 VA of apparent power to produce only 72.60 watts of real, usable work. In other words at 46% power factor, the coil takes about 70% more current to do the same work. This is significant amount of wasted current that doesnt contribute to actual work.

Conclusion

Power in AC Circuits

In this article we saw, how the 3 key players in AC power – real power (P), reactive power (Q), and apparent power (S) can be visualized using a right angled triangle called the power triangle. The sides of this triangle represent these power components, and their relationship is expressed by the formula:

S² = P² + Q²

Here:

Power Factor

We also learned the concept of power factor (p.f.). This crucial parameter indicates, how efficiently an AC circuit utilizes the delivered power. Its calculated as the ratio of real power (P) consumed by the circuit to the apparent power (S) supplied by the source. Mathematically this transforms to:

Power Factor (p.f.) = Real Power / Apparent Power = W / VA

Power factor, is typically expressed as a decimal (e.g., 0.95) or a percentage (e.g., 95%).

The Power Factor Angle

The cosine of the phase angle (Φ) between the current and voltage waveforms in the circuit is directly related to the power factor. Heres the connection:

Power Factor in Real-World Circuits

In practical AC circuits, the power factor can range from 0 to 1.0, depending on the type of load connected.

Importance of Power Factor

A low power factor (closer to 0) signifies wasted power and reduced efficiency. This is because, a circuit with a low power factor necessitates a higher current to deliver the same amount of real power compared to a circuit with a high power factor (closer to 1.0 or unity). Thus, improving the power factor causes a more efficient utilization of power in AC circuits.

References: Power Triangle